Where Should Fixed Combustible Gas Detectors Be Installed?

In industrial production, warehousing, logistics, and public safety scenarios, fixed gas detectors are increasingly widely used. They can monitor the presence of flammable gases such as Methane, Propane, Hydrogen, and Carbon Monoxide in the air in real time, effectively preventing accidents like fires and explosions. However, many users often face a common question when installing these devices: "Where should fixed combustible gas detectors be installed to maximize their effectiveness?" GasDog will systematically explain the installation principles, characteristics of different gases, typical application sites, and common misconceptions to help you install these devices scientifically and rationally.

1. Importance of Installation Location

Fixed combustible gas detectors are preventive safety devices—they do not eliminate gas leaks but instead alert personnel to take action through monitoring and alarms. If installed in the wrong location, even the highest-performance detector may fail to detect a leak in time, rendering it ineffective.

For example:

  • If Methane leaks near the ceiling but the gas detector is installed at ground level, it may not respond until the gas has diffused downward.
  • Conversely, if liquefied petroleum gas (LPG) accumulates near the floor but the gas detector is installed too high, the alarm may be delayed.

Thus, selecting the correct installation location is crucial for ensuring detection efficiency.

2. General Principles for Installation Location

2.1 Installation Height Based on Gas Density

  • Lighter-than-air gases (e.g., Hydrogen, Methane) tend to rise. Fixed gas detectors should be installed above potential leak points, typically 30–60cm from the ceiling.
  • Heavier-than-air gases (e.g., Propane, Butane, LPG) tend to sink. Detectors should be installed 30–60cm from the floor.
  • Gases with a similar density to air (e.g., Carbon Monoxide) should be installed at breathing height (1.5–1.8m).

2.2 Proximity to Potential Leak Sources

  • Install gas detectors near high-risk areas such as valves, flanges, storage tank connections, and gas pipe joints.
  • Avoid placing them directly at gas outlets to prevent sensor damage from high-concentration exposure.

2.3 Ensure Proper Airflow

Fixed combustible gas detectors should be installed in well-ventilated areas so that leaked gas can quickly reach the sensor. Good airflow helps the detector respond faster to potential leaks, reducing the risk of dangerous gas accumulation.

2.4 Avoid Interference Sources

Keep gas detectors away from strong drafts, electromagnetic interference, and high-temperature sources (e.g., steam pipes, heaters) to prevent false readings. Placing detectors too close to these interference sources may cause inaccurate measurements or frequent false alarms.

2.5 Accessibility for Maintenance

Install detectors in easily accessible locations for routine checks, calibration, and part replacement. Convenient access ensures timely maintenance, which is critical to keeping the gas detection system reliable and effective.

3. Combustible Gas Detector Installation Recommendations

  • Industrial Plants: In chemical, petroleum, and metallurgical plants, fixed gas detectors should be placed based on process flow and hazard zoning, particularly near reactors, storage tanks, compressor rooms, and pump rooms.
  • Gas Boiler Rooms: Natural gas detectors should be installed near the ceiling, while LPG detectors should be placed near the floor, close to gas pipelines and valves.
  • Underground Parking Lots: CO detectors should be installed at 1.5m, while LPG detectors should be placed near the ground.
  • Warehouses & Logistics Centers: Install gas detectors in main aisles, valve areas, and storage zones to quickly detect leaks from containers.
  • Laboratories & Research Facilities: In labs using hydrogen, acetylene, etc., detectors should be placed near workbenches and gas cylinder storage areas, integrated with ventilation systems.

4. Quantity and Distribution of Gas Detectors

A single gas detector is often insufficient—multiple units should be strategically placed based on:

  1. Coverage Radius: Typically 7–15m per detector, depending on ventilation.
  2. High-Risk Zones: Priority should be given to areas with higher leak potential.
  3. Multi-Level Spaces: Install fixed combustible gas detectors at different heights in tall or layered environments.

5. Common Mistakes

Prioritizing Aesthetics Over Function
A frequent mistake in gas detector or monitor installation is giving too much importance to aesthetics or design preferences rather than functionality. For example, some facility managers prefer to place detectors in corners, behind furniture, or in concealed areas to keep them “out of sight.” While this may improve the appearance of the room, it can severely compromise safety. Gas detectors must be installed where gas leaks are most likely to occur and where airflow allows for early detection. Placing them in hidden or obstructed spots may cause dangerous delays in identifying leaks. In the worst cases, this could lead to hazardous gas accumulation before the detector is able to trigger an alarm.

Installing Only One Detector
Another common mistake is assuming that a single detector is enough to safeguard an entire building or facility. In reality, large environments such as factories, underground parking lots, or warehouses often have multiple gas sources and areas where gases can accumulate. Installing only one detector leaves blind spots and increases the risk of undetected leaks. Instead, a proper gas detection system should include multiple detectors strategically distributed across high-risk zones, ventilation points, and enclosed spaces. Coverage must be comprehensive to ensure that no dangerous pockets of gas go unnoticed.

Neglecting Maintenance
Even the best-positioned detectors cannot perform reliably if they are not properly maintained. Dust, dirt, humidity, and temperature fluctuations can all affect the sensitivity of sensors over time. Without regular calibration, detectors may give false alarms or, worse, fail to detect actual leaks. Routine cleaning, inspection, and calibration are therefore essential parts of a safe gas monitoring program. Many manufacturers recommend scheduled servicing every 6–12 months, depending on the operating environment. By neglecting maintenance, facility operators risk creating a false sense of security, leaving employees and assets unprotected in critical situations.

6. Conclusion

The installation location of fixed combustible gas detectors directly impacts their effectiveness and safety value. Proper placement requires considering gas density, leak sources, airflow, and maintenance accessibility. Different environments demand specific installation heights and quantities.

By following these principles and performing regular maintenance and calibration, fixed combustible gas detectors can truly serve as reliable "safety sentinels," providing robust protection for industrial operations and daily life.